Hearth and Home Technologies Ventilation Hood TR342 User Manual |
Installation
Instructions
TM
Models:
TR342, TR344, TV342
Round Termination Cap and
Storm Collar
These chimney termination caps have been tested for use with specific Hearth & Home Technologies inc. fireplaces and
are UL listed as fireplace parts. Refer to the installation instructions supplied with the fireplace for the correct accessories
to be used. Check with your local building code agency before you begin installation to ensure compliance with local codes,
including the need for permits and follow-up inspections. If you encounter any problems regarding code approvals, or if you
need clarification of any of the instructions contained here, contact the Heatilator Technical Services Dept., Hearth & Home
Technologies Inc., phone 1-800-927-6841 or 1-888-427-3973.
Note: An arrow (ꢀ) found in the text signifies change in content.
CAUTION
Sharp Edges
•
Wear protective gloves and safety
glasses during installation.
Description
Termination Cap
Storm Collar
Qty
1
1
Fastener Package
1
32 in.
(813 mm)
32-3/8 in.
(822 mm)
34-1/4 in.
(870 mm)
15-3/4 in.
(400 mm)
34-3/8 in.
(873 mm)
TV342
ꢀ
TR342
TR344
Note: The chimney must extend at least 3 ft (.91 m) above the highest point where it passes through the roof and at least
2 ft (.61 m) above any portion of the building within 10 ft (3.05 m). These minimum distances comply with national code
construction requirements but do not guarantee smoke free operation.
Hearth & Home Technologies Inc. • TR342/TR344 Term Cap • 31445 Rev H • 03/06
1
ꢀ
B. TR342 and TV342 Telescoping Round Termination Cap
•
The uppermost chimney section must terminate no more than 14-1/2 in. (368 mm) below the top of the flashing collar on
the chase top. See Figure 3 for additional details.
•
Position the telescoping round termination cap above the collar of the chase top and lower the cap assembly until the
stainless steel telescoping slip section engages a minimum of 4 in. (102 mm) into the uppermost chimney section. Push
the termination cap down until the three support brackets contact with the chase top collar.
Attach the three support brackets to the chase top collar with the screws provided.
Wrap the storm collar around the outer slip section.
•
•
Fasten the ends of the storm collar together with a
screw at the bottom and a nut and bolt through the
Storm Collar
2 in. (51 mm) min.
clamp lock at the top. Slide the storm collar down
until it contacts the chase top and tighten the clamp
lock.
Flashing Collar
•
Caulk the gaps between the outer slip section
and the top of the storm collar to prevent leaks.
Any seams along the storm collar must also be
sealed.
14-1/2 in.
(368 mm) max.
Note: To protect against the effect of corrosion
on those parts exposed to the weather, the
termination cap can be painted with a rust-
resistant paint.
Top of Pipe
1-1/2 in. (38 mm) min.
overlap
Figure 3
I
nstalling TR342, TV342 Round Telescoping Termination Cap
(TR342 shown)
C. Shrouds
•
Field Constructed Shrouds
-
Different shroud designs have been tested for Hearth Technologies fireplace systems using the TR342 and TR344
termination caps. These shrouds may be field constructed if the dimensional requirements specified in Table 1 are
maintained. Some examples are shown in Figure 4. These shrouds must be constructed from a minimum .018 in.
(26 ga) thick aluminized steel. The wire mesh is optional but recommended and must be .018 in. thick minimum
aluminized steel with a maximum 1/2 in. (13 mm) mesh opening.
-
The TR-TVK Round Termination Top Vent Kit is available to reduce the minimum sizes required for shrouds. See
Table 1.
17-1/2 in.
(444 mm)
Dia. centered
3/4 in.
(19 mm)
17-1/2 in.
(444 mm)
Dia. centered
*
3-3/4 in.
(95 mm)
17-1/4 in.
(438 mm)
28-1/4 in.
(718 mm)
*
3 in. (76 mm)
(4 sides)
*
3 in.
(76 mm)
*
*
2 in.
(51 mm)
* See Table 1 for measurements
Figure 4
Shroud Dimensions
ꢀ
•
Installation of the Shroud
•
•
•
Center the hole in the bottom pan (if required) of the shroud over the termination cap and lower the shroud down to
the chase top.
Be sure to keep the shroud centered over the chimney termination and fasten the shroud to the chase top with
screws.
Be sure to caulk or seal around the screw heads to prevent leaks.
Hearth & Home Technologies Inc. • TR342/TR344 Term Cap • 31445 Rev H • 03/06
3
ꢀ
TABLE 1
TV342
TR342/TR344*
TV11/TV11T
TR11/TR11T*
(* with TR-TVK installed)
TS345/T445
(Top Vent)
TR342/TR344
TR442/TR444
TR442/TR444*
(* with TR-TVK installed)
Shroud
TR11/TR11T
OPEN TOP with solid sides and 3 in. (76 mm) opening at the bottom
28 x 28 in.
32 x 32 in.
Mnimum Base
Dimensions
23 in. x 23 in.
(584 x 584 mm)
26 x 26 in.
(660 x 660 mm)
26 x 26 in.
(660 x 660 mm)
(711 x 711 mm)
(813 x 813 mm)
with Radiation Shield
with Radiation Shield
Minimum Top
Dimensions
20 x 20 in.
(508 x 508 mm)
25 x 25 in.
(635 x 635 mm)
23 x 23 in.
(584 x 584 mm)
29 x 29 in.
(737 x 737 mm)
23 x 23 in.
(584 x 584 mm)
MAILBOX STYLE with open ends and 3 in. (76 mm) opening at the bottom of the sides.
28 x 30 in.
26.5 x 28 in.
(673 x 711 mm)
with Radiation Shield
34 x 34 in.
(711 x 762 mm)
with Radiation Shield or
34 x 34 in.
Minimum Base
Dimensions
28 x 30 in.
(711 x 762 mm)
N/A
N/A
(864 x 864 mm)
with Radiation Shield
(864 x 864 mm)
28 1/4 in.
(718 mm)
27 1/2 in.
(699 mm)
28 1/4 in.
(718 mm)
27 1/2 in.
(699 mm)
Minimum Height
ROOFED STYLE with 12 x 22 in. (264 sq. in.) (305 x 559 mm) opening on each side and 3 in. (76 mm) space between the
radiation shield and chase top.
27 x 27 in.
27 x 27 in.
34 x 34 in.
34 x 34 in.
Minimum Base
Dimensions
N/A
N/A
(686 x 686 mm)
(686 x 686 mm)
(864 x 864 mm)
(864 x 864 mm)
with Radiation Shield
with Radiation Shield
with Radiation Shield
with Radiation Shield
23 in.
(584 mm)
23 in.
(584 mm)
23 in.
(584 mm)
23 in.
(584 mm)
Minimum Height
Minimum Height is measured from the bottom of the termination cap:
Minimum height is established with the bottom of the termination cap 7 in. (178 mm) above the chase top. Minimum height must increase
accordingly for any height above 7 in. (178 mm).
All dimensions are INSIDE dimensions.
4
Hearth & Home Technologies Inc. • TR342/TR344 Term Cap • 31445 Rev H • 03/06
|